§1 · The three-phase system
Three sources, four voltage names
A balanced three-phase source consists of three sinusoidal sources of equal magnitude whose phases are displaced by 120°. In the positive sequence, which is also called the abc sequence and is assumed throughout this lecture, the three phase voltages are
Their sum vanishes, which is the algebraic fact behind everything that follows: .
Every quantity on this page is a phasor, written with a tilde, and every impedance is complex. Magnitudes are RMS values unless stated otherwise, so that the power formulas need no factor of one half. A time-domain source therefore becomes .
The Y-Y system below carries the vocabulary of the lecture. Four different voltages are named, and confusing them is the most common source of error in three-phase work:
Lower-case letters name the source terminals and upper-case letters name the load terminals, exactly as in the board notes. A phase voltage is measured from a line terminal to the neutral point, and a line voltage is measured between two line terminals. The three line impedances model the conductors that connect the source to the load. Figure labels omit the phasor tilde for legibility; the equations retain it.
Because the three source voltages sum to zero and the three load branches are identical, the three line currents also sum to zero, so the neutral conductor carries no current at all. It may therefore be removed, or replaced by any impedance whatsoever, without altering a single voltage or current in the balanced circuit. This observation is what makes the single-phase equivalent of Section 2 legitimate.
§2 · The single-phase equivalent
One loop replaces the whole system
Because the neutral point of the source and the neutral point of the load are held at the same potential, each phase may be extracted and solved on its own. The result is an ordinary single-loop AC circuit, and the remaining two phases follow by rotation rather than by further analysis.
The extracted phase
Phase a is cut out of the system: the source, the line impedance, the load impedance, and the neutral return that joins n to N. The animated dots represent the line current .
KVL around the single loop
The two impedances carry the same current, because the loop admits only one.
Solve for the line current
The load phase voltage follows at once as , which is smaller than by the drop across the line.
The other two phases are rotations
Only one calculation is ever performed. The three line currents have equal magnitudes and are separated by 120°, and they sum to zero.
The current that leaves terminal a on the line is the very same current that passes through the source phase and through the load branch , because those elements lie in series. This identity is the first half of the Y-Δ comparison assembled in Section 5.
§3 · The line voltage
Line to line: a factor of √3 and a 30° lead
The line voltage is defined between two line terminals, so it is obtained from two phase voltages by KVL rather than read off a single source. The derivation below is performed once for ; the other two line voltages follow by rotation.
The quantity to be found
The line voltage is the potential of terminal a relative to terminal b. No single element spans those two terminals, so a loop equation is required.
KVL around the a-n-b loop
The loop is traversed from the neutral point up through the a phase, across the terminals, and back down through the b phase.
Positive sequence removes the second unknown
The bracket is a pure number, identical for every balanced positive-sequence system, so it is worth evaluating once and remembering.
Evaluate the bracket
The relation, at the source and at the load
Nothing in the derivation referred to the source, so the same relation holds at the load terminals. The remaining line voltages are rotations of the first: lags by 120°, and leads it by 120°.
The three phase voltages , , and form a symmetric star. The line voltage is constructed as , drawn dashed, and the completed parallelogram makes the two conclusions visible at once: the line voltage is longer by and it leads by 30°.
A 120 V rms phase voltage produces a line voltage of V rms, which is the familiar 120/208 V service. The 277/480 V service is the same rule applied again: V.
§4 · The Δ circuit
The dual relation, carried by the currents
In a Δ connection the three elements are joined end to end in a triangle, and the three line terminals are the corners. The consequence is the exact dual of the Y result: the line voltage is now the phase voltage itself, while the line current differs from the phase current by .
The Δ load
Each impedance is connected directly between two line terminals, so the voltage across it is a line voltage: appears across the branch from A to B. The currents , , and circulate inside the triangle and are the phase currents; the currents , , and arrive on the lines.
KCL at the corner
The dashed surface encloses corner A. One current arrives on the line, one leaves into the A-B branch, and one arrives from the C-A branch.
Positive sequence removes the second unknown
The phase currents inherit the sequence of the voltages that drive them, because all three branches carry the same impedance.
Evaluate the bracket
The bracket is the complex conjugate of the one obtained in Section 3, so the magnitude is again and the shift is again 30°, but of opposite sign.
The relation
The line current is larger by and lags the phase current by 30°.
The current diagram of the Δ load mirrors the voltage diagram of the Y source. The phase currents , , and form the star, and the line current is completed by adding the dashed to .
§5 · Δ against Y
Which quantity is shared, and which is transformed
One rule per connection is sufficient, because the other quantity is then the one that carries the factor. The two rules are mirror images:
Δ: line V = phase V, line I ≠ phase I
Y: line I = phase I, line V ≠ phase V
The three branches meet at a neutral point, so each branch carries its own line current. The line voltage spans two branches and therefore acquires the factor.
Each branch is connected directly between two line terminals, so each branch sees a line voltage. The line current splits between two branches and therefore acquires the factor.
Converting a load between the two connections
A balanced Δ load and a balanced Y load are interchangeable, and the transformation is the balanced Y-Δ rule of Lecture 2 with resistances replaced by impedances:
Converting a Δ load to its Y equivalent is the standard first move, because the single-phase equivalent of Section 2 requires a Y load and a neutral point to work with.
The Δ connected source
The three sources are joined into a closed triangle, and the terminals a, b, and c are the corners. The source phase voltage is the line voltage itself, which is the defining property of the Δ source.
A Δ source may also be replaced by an equivalent Y source, whose phase voltage is obtained by inverting the relation of Section 3:
The quantity computed above is a Δ-Y conversion equivalent voltage only. The actual phase voltage of the Δ source remains the line voltage , and any power calculation performed on the source itself must use that value. The equivalent is legitimate for finding line currents and load quantities, which is exactly what it is built for.
§6 · Balanced three-phase power
One phase, then multiply by three
The complex power of a single phase follows the same three forms as in single-phase AC analysis, with and taken across and through one load branch:
For a balanced system the three phases are identical, so the total is three times the single-phase result:
The two practical specializations are worth writing out, because each avoids a conversion step. For a Y load the line current is the phase current, and for a Δ load the line voltage is the phase voltage:
Substituting either rule of Section 5 into gives one expression that holds for both connections: , with and , where is the angle of the load impedance. The appears exactly once, whichever connection is in use.
The power triangle
The line voltage is held at 208 V rms below. The current slider scales the triangle, and the impedance angle divides the apparent power between the real power and the reactive power. A positive angle denotes an inductive load, which absorbs reactive power.
The horizontal leg is the real power , the vertical leg is the reactive power , and the hypotenuse is the apparent power . The power factor is the cosine of the angle at the origin.
|S3φ| = kVA P3φ = kW Q3φ = kvar pf =
A load at draws the same line current as a load at yet converts only half of the apparent power into real power. The line loss, which depends on the current alone, is unchanged. This is the whole motivation for power factor correction, and it is why utilities meter reactive power separately.
§7 · Worked example A: three line currents and the load power
A Y-Y system specified in the time domain
The problem
A Y-Y, three-phase, positive-sequence system has the a-phase source voltage V, a line impedance of 10 Ω, and a load consisting of a 40 Ω resistor in series with a 40 mH inductor. The three line currents and the real power delivered to the load are required.
Phasors first
The RMS convention is adopted because the source amplitude was written as , which is exactly the form that produces a round 100 V rms.
One division delivers the a-phase current
The current lags the source voltage, as an inductive load requires.
The other two currents are rotations
Each is obtained from by subtracting and adding 120° respectively, which is the whole benefit of the balanced assumption.
The real power delivered to the load
Only the resistive part of appears, because the inductor absorbs no real power. The reactive part gives var.
Check: the source supplies exactly what the load and the line consume
The three line resistances absorb W, so the load and the line together require 550 W. The source delivers
The real parts agree at 550 W, and the reactive parts agree at 166 var, since the line is purely resistive here and the inductor is the only reactive element. ✓
Truncating the current to 1.9 A before squaring gives W, an error of 7 W on a 440 W answer. Magnitudes should be carried at full precision until the final multiplication, because the power formulas square them.
§8 · Worked example B: starting from the load voltage
When the given quantity sits at the far end
The problem
A three-phase, Y-Y, positive-sequence system has a line voltage at the load of 100 V rms, a line impedance of 10 Ω, and a Y-connected load impedance of . The real power delivered to the load is required.
The line impedance is not needed
The load voltage is given directly, so the source voltage never enters the calculation. The 10 Ω line impedance would be required only if the source voltage were the given quantity, or if the line loss were requested.
Convert the load to Δ, so that the line voltage is the phase voltage
The conversion is worth the one line it costs: the given line voltage becomes a phase voltage of the Δ equivalent, so no factor is needed anywhere in the calculation.
Rationalize and take the real part
The answer
The reactive part follows from the same fraction: var.
Independent check: the same answer through the Y load
The Y route uses the phase voltage at the load, which is smaller than the line voltage by :
Two routes that share no arithmetic reach the same number, which is the strongest check available. As a further remark, the source voltage may now be recovered if desired: V rms, a line voltage of 122.2 V rms at the source.
§9 · Your turn
Practice: a Δ load behind a line impedance
The problem below combines every result of the lecture: a Δ load must be converted, a single-phase equivalent must be solved, and a phase current must be recovered from a line current. It should be attempted on paper before the hints are opened, in order.
A balanced Δ load of per branch is fed through three line impedances of from a Y-connected, positive-sequence source with V rms. Find the line current , the load phase current , and the total real power delivered to the load.
Hint 1: Make the load a Y
The single-phase equivalent needs a neutral point, and a Δ load has none. Convert first: . The line impedance is not touched by the conversion, because it lies outside the load.
Hint 2: Solve one phase
The per-phase loop of Section 2 gives . The line current is unchanged by the Δ-Y conversion, which is precisely why the conversion is legitimate.
Hint 3: Return to the Δ for the phase current
Section 4 gives , so the phase current is recovered by dividing. For the power, either or may be used; they must agree.
Solution
The Y equivalent of the load is , so the per-phase loop carries and
The real power delivered to the load, computed on the Δ branches and then independently on the Y equivalent:
A third check closes the accounting. The three line resistances absorb W, while the source supplies W, and W ✓. The load line voltage, if wanted, is V rms.